Technical Data |
TM-8200s |
TM - 8300s |
|
Measurement |
True RMS |
|
Current Rating (lE) |
5A |
|
Current Setting Range (lE>) |
2% - 50% |
| Time
Setting Range (tlE>) |
0.05 - 10.0 sec
(0.1 sec step) |
0.05 - 10.00 sec
(0.01 time multiplier) |
| High Set Range (lE>>) |
10% - 500% |
2 - 990% or OFF |
| High
Set Time Setting Range (tlE>>) |
Fixed at 50 ms |
0.05 - 10.0
(0.1 sec
step) |
| IDMT
Graph |
Normal Inverse : 3.0 /
10
Normal Inverse : 1.3 / 10
Very Inverse
Extremely Inverse (standard)
Extremely Inverse (0.64)
Long Time Inverse |
| Relay
Operation Level |
ln / ls >= 1.0 |
ln / ls >= 1.0 |
|
Display Range (ln) |
0.0% ~ 500% |
0.0% ~ 990%
>990% display 'out' |
| Min
Sensitivity |
approx. 0.5% |
|
Tripping Contact |
|
SPDT 5A/240V AC |
K1
: Latching |
| K2
: Programmable |
|
| Power
Supply |
240V AC, 50 Hz
(Optional: 110VAC 50 Hz) |
240V AC, 50/60 Hz
(Optional: 110VAC 50/60 Hz) |
| C.T.
Input / Burden |
.../5A / 1VA |
| Weight |
approx. 600g |
|
Ambient Temperature |
0°C to +70°C |
|
Standard |
IEC 1000-4-4, IEC
1000-4-5, IEC 255-5 |